📄 Check Fast : OUT0+OUT1

Check Fast : OUT0+OUT1


Check the setting for FAST = OUT0+OUT1: it needs to be on YES

see the video below : 

password is 2234



you can check the optimal working as follows : 

  • set the target weight to 7kg
  • set the pre-fast to 2kg
  • test a filling cycle with a known weight of 5kg: after 5kg, the valve should switch from fast to slow on the display

if the valve closes at the same time as the fast to slow switch follow this tutorial